The most common fault problem of the swing gate is that the gate will not be reset after opening the gate, or will be reset immediately after opening the gate. So, how should we solve this phenomenon? The specific fault analysis, the following are the common swing gate fault solution for your reference!
Problem: The gate does not reset after the gate is opened or resets immediately after it is opened. When the pedestrian passes the gate, the gate is not immediately reset (referring to the gate with induction reset function). After a delay, the gate is locked or Immediately after an open position reset: Swing gate detection method: first detect the cylindrical photoelectric switch and whether it is on; when the signal output, the L2 or L4 indicator on the motherboard will become bright, otherwise the motherboard is damaged; check whether the main board parameter setting P08 is set to With memory.
Problem: After the swing gate gives a valid gate open signal, the gate does not operate. 1) The main board indicator is normal. When a valid gate signal is given, the L7 or L8 indicator will flash intermittently and the direction indicator will turn into a green arrow (2 points are included here. Signals in different directions): No function of the swing gate sensor: Detection method: Detect the output voltage of the PC and PD of the PX terminal (AC18V), and check whether the fuse of the F2 (3A) is blown; if it is normal, check the MA and MB of the DX terminal. Is there a voltage output (DC24V) at both ends, and if there is an output, check whether the motor connection is disconnected; if the motor is damaged;
2) The main board indicator light is off, LED digital tube is not displayed:
Detection method: Detect the voltage output of the PX terminal's PA and PB (AC12V); detect whether the F1 (2A) fuse is blown. If all of the above are normal, it is determined that the motherboard is damaged;
Problem: The two gates are not synchronized when the swing gate is open. 1) The two swing gates have different time settings (see the system parameter setting operation instructions). Check the P03, P17 time parameters.
2) Check the line, if the line is loose or unwelded.
Shenzhen Xintongengeng Technology Development Co., Ltd. is a high-tech enterprise that integrates advanced foreign technology, research and development, production, sales and service. It specializes in providing high-quality three-roll gates, swing gates, wing gates, and all gate gates And other products, welcome to inquire.
Problem: The gate does not reset after the gate is opened or resets immediately after it is opened. When the pedestrian passes the gate, the gate is not immediately reset (referring to the gate with induction reset function). After a delay, the gate is locked or Immediately after an open position reset: Swing gate detection method: first detect the cylindrical photoelectric switch and whether it is on; when the signal output, the L2 or L4 indicator on the motherboard will become bright, otherwise the motherboard is damaged; check whether the main board parameter setting P08 is set to With memory.
Problem: After the swing gate gives a valid gate open signal, the gate does not operate. 1) The main board indicator is normal. When a valid gate signal is given, the L7 or L8 indicator will flash intermittently and the direction indicator will turn into a green arrow (2 points are included here. Signals in different directions): No function of the swing gate sensor: Detection method: Detect the output voltage of the PC and PD of the PX terminal (AC18V), and check whether the fuse of the F2 (3A) is blown; if it is normal, check the MA and MB of the DX terminal. Is there a voltage output (DC24V) at both ends, and if there is an output, check whether the motor connection is disconnected; if the motor is damaged;
2) The main board indicator light is off, LED digital tube is not displayed:
Detection method: Detect the voltage output of the PX terminal's PA and PB (AC12V); detect whether the F1 (2A) fuse is blown. If all of the above are normal, it is determined that the motherboard is damaged;
Problem: The two gates are not synchronized when the swing gate is open. 1) The two swing gates have different time settings (see the system parameter setting operation instructions). Check the P03, P17 time parameters.
2) Check the line, if the line is loose or unwelded.
Shenzhen Xintongengeng Technology Development Co., Ltd. is a high-tech enterprise that integrates advanced foreign technology, research and development, production, sales and service. It specializes in providing high-quality three-roll gates, swing gates, wing gates, and all gate gates And other products, welcome to inquire.
Energy Abosorbing Lanyard is a connection between Full Body Harness and fixed point. It made of high strength polyester rope. One end with normal karabiner for connect harness, the other end with one or tow big hook. The hook can be connect with fixture. And it with Energy Absorb unit.
It used for high-altitude workers.
Energy Absorbing Lanyard,Shock Absorber Lanyard,Safety Lanyard With Shock Absorber,Safety Lanyard With 2 Hooks
Greateagle Safety Products Co., Ltd. , https://www.greateaglesafety.com